Data Center PUE, CUE and WUE
Compare energy, emissions and water use per unit of IT energy over a common period and facility boundary
Results
—
- CUE
- —
- WUE
- —L/kWh
- CUE category
- —
- Reporting days
- —days
Results update automatically when the required values are entered.
Method, applicability and sources
Calculation method
For the same facility boundary and 12 consecutive months: PUE = total facility energy (kWh) / IT energy (kWh); CUE = verified operational CO₂ or CO₂-equivalent emissions (kg) / IT energy (kWh); WUE = net water use (m³) ×1000 / IT energy (kWh). WUE in L/kWh is numerically equivalent to m³/MWh. Net water = withdrawals − returned water. Confirm numerator boundaries separately under the standard's measurement category.
Worked example (hypothetical values)
Hypothetical example: January 1–December 31, 2025; facility energy 1,800,000 kWh, IT energy 1,200,000 kWh, category 2 emissions 720,000 kgCO₂e, net water 1,800 m³. PUE =1.5; CUE =0.6 kgCO₂e/kWh; WUE =1.5 L/kWh.
Applicability and limitations
Twelve consecutive months of operational data for one data center or a facility whose usage can be metered separately from other uses. Does not impute missing measurements or allocations, select emission factors, convert generation/fuel/heating/cooling to kWh, classify WUE categories, certify measurement-category compliance, annualize short periods or simply average multiple facilities. Do not mix boundaries or periods.
Method and sources
Method: PUE: ISO/IEC 30134-2:2026 §5.1 / CUE: ISO/IEC 30134-8:2022 §§5 and 6.2.2 / WUE: ISO/IEC 30134-9:2022 §§5 and 6.2. Data recorded: 2026-11-13.