4–20 mA and Voltage Scaling with Square-Root Extraction

Report an issue

Define an instrumentation signal range and convert to or from the corresponding physical quantity

Square-root extraction is an ideal mapping from an unsquare-rooted differential-pressure signal to a flow-proportional value. Do not apply square-root extraction to a signal already processed this way.

What to calculate

Enter 4 for 4–20 mA or 1 for 1–5 V.

The upper limit must exceed the lower limit.

For example: kPa, m³/h or °C. Use the same units for the range and entered value.

Use Linear for a flow-proportional signal already square-rooted by the transmitter.

Results

Results update automatically when the required values are entered.

Method, applicability and sources

Calculation method

Normalize the signal: x = (signal value − lower signal limit) ÷ (upper signal limit − lower signal limit). Linear: physical quantity = lower engineering limit + engineering span × x. Square root: physical quantity = lower engineering limit + engineering span × √x (x≥0). For inverse linear conversion, x = (physical quantity − lower engineering limit) ÷ engineering span; for inverse square-root conversion, square that normalized value. Signal value = lower signal limit + signal span × x. Values outside the configured range are extrapolated, not clamped. Low-flow cutoff and device-specific processing are excluded.

Worked example (hypothetical values)

For ranges of 4–20 mA and 0–100 m³/h, linear scaling maps 12 mA to 50 m³/h. With square-root extraction of a differential-pressure-proportional signal, 8 mA maps to 50 m³/h, and inverse conversion from 50 m³/h gives 8 mA.

Applicability and limitations

When the range endpoints of an analog current/voltage instrument signal and the corresponding engineering units are defined. Excludes transmitter-specific piecewise functions, low-flow cutoff, saturation, open-circuit/fault-current detection, temperature-sensor conversion equations and density/temperature/pressure compensation.

Methods used

  • Linear scaling and inverse conversion (v1.0): scope Linear mapping between range endpoints; out-of-range values are extrapolated; region Global
  • Ideal square-root scaling and inverse conversion (v1.0): scope An unsquare-rooted signal proportional to differential pressure; no low-flow cutoff or device-specific corrections; region Global

Method and sources

Method: E238 ideal normalized scaling v1.0 (2026-11-13). Data recorded: 2026-11-13.