Wire Voltage Drop and Conductor Resistance
Calculate conductor resistance and resistive voltage drop in two-wire DC, two-wire single-phase, and balanced three-wire three-phase circuits.
AC results approximate only the resistive component at power factor 1 with line reactance neglected. Three-phase results are line-to-line drops in balanced three-wire circuits.
This tool does not assess ampacity or compliance with laws and standards.
Results
—V
—Ω
- Round-trip two-wire resistance
- —Ω
- Temperature-corrected resistivity
- —Ω·mm²/m
- Single-conductor resistance at 20 °C
- —Ω
- Drop as a percentage of nominal voltage
- —%
Results update automatically when the required values are entered.
Method, applicability and sources
Calculation method
Let ρ20 be resistivity at 20 °C (Ω·mm²/m), T conductor temperature (°C), α20 the temperature coefficient (1/°C), L one-way length (m), A cross-sectional area (mm²), and I current (A). ρ(T)=ρ20×[1+α20×(T−20)]; resistance of one conductor R(T)=ρ(T)×L/A. For two-wire DC or single-phase, voltage drop ΔU=2×I×R(T). For balanced three-wire three-phase, line-to-line drop ΔU=√3×I×R(T). If nominal voltage U is supplied, percentage drop=ΔU/U×100%. The AC approximation uses power factor 1 and reactance 0, rather than the general AC-system voltage-drop equation.
Worked example (hypothetical values)
Hand-calculation example: IACS copper with ρ20=0.01724 Ω·mm²/m, one-way length 30 m, area 2.5 mm², temperature 20 °C, and current 10 A in a two-wire DC circuit gives single-conductor resistance 0.20688 Ω, round-trip resistance 0.41376 Ω, and voltage drop 4.1376 V. At nominal 100 V, the drop is 4.1376%.
Applicability and limitations
A single wire segment with known length and area and specified conductor resistivity and temperature. Three-phase circuits must be balanced, with identical conductor conditions and currents in each phase. Excludes AC power factors other than 1, line reactance, skin/proximity effects, harmonics, imbalance, different outgoing/return conductors, joint resistance, temperature gradients, ampacity, short-circuit protection, and electrical-code compliance.
Methods used
- Conductor resistance and resistive voltage drop for two-wire / balanced three-phase circuits (v1.0 / JICA DS15-1 (2003); Seattle SPU Appendix 9C (2024)): scope Constant cross section, uniform temperature, identical conductor material, and constant current. AC assumes balanced sinusoids, power factor 1, and negligible line reactance.; region Global
Method and sources
Method: DC Resistance and Linear Temperature Correction v1.0 (JICA DS15-1 2003 / Seattle SPU DSG 2024). Data recorded: 2026-11-13.
- JICA / J-POWER & CEPCO, Guidebook for Power Engineers, DS15-1 (2003), conductor properties table
- Seattle Public Utilities, Design Standards and Guidelines Appendix 9C, §6.8 Voltage Drop (2024)
- Hong Kong Electrical and Mechanical Services Department, Technical Guidelines on Code of Practice for Energy Efficiency of Building Services Installation, §7.8.3 (2021)