Fan Affinity Laws: Speed, Airflow, Pressure, and Power
Compare changes in airflow, pressure, and shaft power when changing the speed of the same fan.
A reference calculation for the same fan and air conditions, with duct-system resistance approximately proportional to the square of airflow. It does not determine equipment ratings or whether operation is permissible.
Results
—m³/min
—kW
- New fan pressure
- —Pa
- Speed ratio (new ÷ reference)
- —×
Results update automatically when the required values are entered.
Method, applicability and sources
Calculation method
Let N₀ be the reference speed and N₁ the new speed (rpm), with speed ratio r = N₁/N₀. Airflow Q₁ = Q₀×r (m³/min), fan pressure Δp₁ = Δp₀×r² (Pa), and fan shaft power W₁ = W₀×r³ (kW). Assumes unchanged fan diameter, air density, pressure type, and resistance characteristics. Does not account for high-pressure compressibility corrections or changes in motor efficiency.
Worked example (hypothetical values)
For reference values of 1,200 rpm, 60 m³/min, fan static pressure 500 Pa, and shaft power 2.4 kW, reducing the speed to 900 rpm gives r = 0.75, airflow 45 m³/min, static pressure 281.25 Pa, and shaft power 1.0125 kW.
Applicability and limitations
Reference comparisons for fans operating at low pressure where an incompressible approximation applies and fan diameter, air density, and system resistance characteristics are unchanged. Excludes intersections of measured fan and system curves, fixed static-pressure components, damper changes, changes in fan diameter or air density, high pressure above 2.5 kPa and compressibility, stall or surge, drive efficiency and electrical energy use, maximum permissible speed, noise and vibration, certified ratings, and performance guarantees.
Method and sources
Method: E106-v1.0 / DOE fan laws; AMCA Publication 211-22 (Rev. 01-23) Annex I. Data recorded: 2026-11-13.