Earth Electrode Resistance and Soil Resistivity Estimates

Report an issue

Compare estimated earth electrode resistance and mutual effects between rods using geometric approximations for homogeneous soil

This is a reference estimate based on geometry in homogeneous soil. Verify actual earth resistance by measurement after installation. The calculated value cannot be used to certify protection against electric shock.

What to calculate

Enter a measured or surveyed value. The value is not inferred from the soil type.

Earth Rod Positions (enter X and Y for each rod when using 2 or more)Optional
RowX coordinate (m) OptionalY coordinate (m) OptionalActions
1

Paste 2 tab-separated columns into the leftmost field. Up to 12 rows.

Coordinates may be omitted for 1 rod. For 2 or more, enter X and Y in every row. Rods are assumed to have the same length and diameter.

Results

Results update automatically when the required values are entered.

Method, applicability and sources

Calculation method

Single rod: R = ρ/[2πL] × [ln(4L/r) − 1], where r = diameter/2. 2 rods: R = (R∞ + Rm)/2, R∞ = ρ/[2πL]ln(2L/r), Rm = ρ/[2πL]asinh(L/d), where d is the distance between rods. Area approximation for 3 or more rods: R = ρ/[2πnL] × [ln(4L/r) − 1 + 2.8L(√n − 1)²/√A], where A is the convex hull area of the rod layout. Straight conductor: R = ρ/[2πL] × [ln(L/r) + ln(L/z) − 2 + 2z/L − (z/L)²]. Ring conductor: R ≈ 2ρ/L. Vertical plate: R = ρ/[2πL] × [ln(8W/(W/2 + t)) − 1]. Wenner method: ρa ≈ 2πaR (b ≤ a/20). All dimensions are converted to m in the formulas.

Worked example (hypothetical values)

FHWA Appendix N: with ρ = 100 Ω·m, 1 rod of length 3 m and diameter 20 mm gives approximately 32.3 Ω. Placing 4 identical rods at the corners of a 3 m square gives approximately 11.7 Ω. A straight conductor of length 50 m, radius 2.52 mm and depth 0.6 m gives approximately 3.93 Ω.

Applicability and limitations

Preliminary evaluation of earth electrodes where apparent or representative soil resistivity is known. Excludes two-layer or multilayer soil, electrode corrosion and contact resistance, combined straight conductors and rods, mutual resistance between rods and plates, resistance of the earthing conductor itself, and measured results after installation. Does not certify touch voltage, step voltage or protection against electric shock.

Methods used

  • Single earth rod, area approximation for multiple rods, buried straight conductor and vertical plate (FHWA-HRT-06-139 (2006), Appendix N, 3.1, 3.3, 3.5 and 3.7): scope Homogeneous soil; noncollinear rod layouts and an area approximation for multiple rods; region Global
  • Mutual resistance of 2 earth rods (Cooley, Mine Grounding Systems (1977), 4.1 and 4.2): scope 2 identical vertical earth rods, homogeneous soil and a line-current model; region Global
  • Buried ring conductor (Schneider Electric Electrical Installation Guide, Chapter E, Fig. E20): scope A closed buried ring conductor in contact with soil; region Global
  • Wenner apparent resistivity (EPRI 3002000596, 4.3, Eq. 4-1): scope 4 equally spaced electrodes, shallow auxiliary electrodes and apparent resistivity; region Global

Method and sources

Method: FHWA-HRT-06-139 (2006), Appendix N; USBM/WVU (1977), Chapter 4; Schneider Electric Electrical Installation Guide, Chapter E; EPRI 3002000596, Chapter 4. Data recorded: 2026-11-14.