Fuel Gas Wobbe Index and Comparison
Calculate the Wobbe index from volumetric heating value and relative density, and compare two gases
Indices are compared at the same reference conditions and heating-value basis. Similar values do not establish equipment interchangeability or safety.
Results
—MJ/m³
- Comparison
- —
- Calculation basis
- —
Results update automatically when the required values are entered.
Method, applicability and sources
Calculation method
Wobbe index W = H / √d. H is volumetric heating value (MJ/m³) on the selected higher (HHV) or lower (LHV) basis; d is dimensionless relative density to dry air at the same reference conditions. kWh/m³ is converted using 1 kWh = 3.6 MJ. Difference ΔW = W(B) − W(A); relative difference = ΔW / W(A) × 100%. Relative difference is undefined when W(A) = 0. No conversion between reference conditions or estimation from composition is performed.
Worked example (hypothetical values)
HHV 38.62077 MJ/m³ and relative density 0.5971935 at 15 °C and 101.325 kPa give a Wobbe index of approximately 49.97622 MJ/m³.
Applicability and limitations
Gases with known heating value and relative density to dry air, measured or calculated at the same reference conditions for volume. Does not convert between reference conditions, estimate heating value or real-gas density from composition, calculate combustion air, or determine fuel compatibility, standards compliance or safety. Comparison does not certify equipment interchangeability.
Method and sources
Method: NBSIR 86-3057(1986)Definitions p.xiii / ISO 6976:2016 §3.5–3.6. Data recorded: 2026-11-14.