Search Tools

Kitchen Hood and Local Exhaust Airflow Calculator

Report an issue

Preliminary exhaust airflow estimates focused on capture at the source.

This estimates exhaust near the source, not whole-room air changes. It does not guarantee equipment safety, regulatory compliance or capture performance.

What to calculate

If equipment under one hood has different duty ratings, select the highest rating.

Horizontal hood length. The calculation uses airflow per unit length, not opening area.

No selection is needed for other hood types.

Results

Results update automatically when the required values are entered.

Method, applicability and sources

Calculation method

Kitchen (listed Type I): Q [cfm] = hood length [m] ÷ 0.3048 × typical value from ASHRAE 2019 Table 5 [cfm/ft] × number of sides (double-island only). Where Table 5 says “or greater,” no upper limit is inferred. Local exhaust (circular or non-slot rectangular): Q [cfm] = k×V [fpm]×(10×x [ft]²+A [ft²]), where k=1 for a plain opening or 0.75 for a flanged opening. In SI units, Q [m³/h] = 3600×k×V [m/s]×(10×x [m]²+A [m²]). 1 ft=0.3048 m; 1 cfm=1.69901079552 m³/h. Intermediate calculations are not rounded; results are displayed to 1 decimal place, or 2 for local exhaust.

Worked example (hypothetical values)

Example: a wall-mounted Type I hood, medium duty, 3.048 m (10 ft) long gives 2000–3000 cfm, approximately 3398–5097 m³/h. A plain opening with area 0.5 m², distance 0.2 m and target velocity 0.5 m/s gives 3600×0.5×(10×0.2²+0.5)=1620 m³/h.

Applicability and limitations

Kitchen: listed Type I hoods with known geometry and highest equipment duty. Local exhaust: specified centerline capture velocity for a single circular opening or rectangular opening with a short-to-long-side ratio of at least 0.2. Does not calculate kitchen Type II or unlisted hoods; effects of enclosure, makeup air, cross-drafts or hood height; equipment-specific listed airflow; or statutory minimums. Local exhaust excludes slot and canopy hoods, thermal plumes, obstructions, duct losses, fan static pressure and statutory control-velocity checks. Do not interpret the exhaust limits in 90.1-2022 as required airflow.

Methods used

  • Typical exhaust airflow for listed commercial kitchen Type I hoods (ASHRAE HVAC Applications 2019 ch.34 Table 5): scope Hood type × highest equipment duty × length (and number of sides for double-island hoods); region Reference values from US publications; Japanese building-services compliance is outside scope.
  • Centerline capture airflow for non-slot openings (AIHA Plain / Flanged Hood Opening Flow Rate): scope Circular openings or rectangular openings with a short-to-long-side ratio of at least 0.2, with a centerline capture point in free space.; region General formula with unit conversion; compliance assessment is outside scope.

Method and sources

Method: ASHRAE Handbook—HVAC Applications 2019 ch.34 Table 5 / AIHA opening hood formulas (cross-checked 2026-11-13). Data recorded: 2026-11-13.