Kitchen Hood and Local Exhaust Airflow Calculator
Preliminary exhaust airflow estimates focused on capture at the source.
This estimates exhaust near the source, not whole-room air changes. It does not guarantee equipment safety, regulatory compliance or capture performance.
Results
—m³/h
- Reference exhaust airflow (US units)
- —cfm
Results update automatically when the required values are entered.
Method, applicability and sources
Calculation method
Kitchen (listed Type I): Q [cfm] = hood length [m] ÷ 0.3048 × typical value from ASHRAE 2019 Table 5 [cfm/ft] × number of sides (double-island only). Where Table 5 says “or greater,” no upper limit is inferred. Local exhaust (circular or non-slot rectangular): Q [cfm] = k×V [fpm]×(10×x [ft]²+A [ft²]), where k=1 for a plain opening or 0.75 for a flanged opening. In SI units, Q [m³/h] = 3600×k×V [m/s]×(10×x [m]²+A [m²]). 1 ft=0.3048 m; 1 cfm=1.69901079552 m³/h. Intermediate calculations are not rounded; results are displayed to 1 decimal place, or 2 for local exhaust.
Worked example (hypothetical values)
Example: a wall-mounted Type I hood, medium duty, 3.048 m (10 ft) long gives 2000–3000 cfm, approximately 3398–5097 m³/h. A plain opening with area 0.5 m², distance 0.2 m and target velocity 0.5 m/s gives 3600×0.5×(10×0.2²+0.5)=1620 m³/h.
Applicability and limitations
Kitchen: listed Type I hoods with known geometry and highest equipment duty. Local exhaust: specified centerline capture velocity for a single circular opening or rectangular opening with a short-to-long-side ratio of at least 0.2. Does not calculate kitchen Type II or unlisted hoods; effects of enclosure, makeup air, cross-drafts or hood height; equipment-specific listed airflow; or statutory minimums. Local exhaust excludes slot and canopy hoods, thermal plumes, obstructions, duct losses, fan static pressure and statutory control-velocity checks. Do not interpret the exhaust limits in 90.1-2022 as required airflow.
Methods used
- Typical exhaust airflow for listed commercial kitchen Type I hoods (ASHRAE HVAC Applications 2019 ch.34 Table 5): scope Hood type × highest equipment duty × length (and number of sides for double-island hoods); region Reference values from US publications; Japanese building-services compliance is outside scope.
- Centerline capture airflow for non-slot openings (AIHA Plain / Flanged Hood Opening Flow Rate): scope Circular openings or rectangular openings with a short-to-long-side ratio of at least 0.2, with a centerline capture point in free space.; region General formula with unit conversion; compliance assessment is outside scope.
Method and sources
Method: ASHRAE Handbook—HVAC Applications 2019 ch.34 Table 5 / AIHA opening hood formulas (cross-checked 2026-11-13). Data recorded: 2026-11-13.