Battery Series/Parallel Configuration and Backup Runtime
Estimate pack voltage and supply duration from the series/parallel cell configuration and a constant-load energy balance
This is an estimate based on rated capacity. Actual UPS runtime depends on battery and equipment discharge characteristics and protective shutdown behavior.
Results
—hours
—V
- Nominal pack capacity
- —Ah
- Nominal energy
- —Wh
- Estimated energy available to the load
- —Wh
- Nominal C-rate required by the load
- —C
Results update automatically when the required values are entered.
Method, applicability and sources
Calculation method
Pack voltage (V) = nominal cell voltage (V)×series count. Pack capacity (Ah) = nominal cell capacity (Ah)×parallel count. Nominal energy (Wh) = pack voltage×pack capacity. Estimated usable energy (Wh) = nominal energy×depth of discharge (%)÷100×discharge-path efficiency (%)÷100. Backup runtime (h) = estimated usable energy÷load (W). Required C-rate (1/h) = load (W)÷discharge-path efficiency as a fraction÷nominal energy (Wh).
Worked example (hypothetical values)
Example: Identical 12 V, 200 Ah batteries connected 2 in series × 2 in parallel give 24 V, 400 Ah, and 9,600 Wh. With 80% depth of discharge, 90% discharge efficiency, and a constant 960 W load, 6,912 Wh÷960 W = 7.2 hours.
Applicability and limitations
Estimate for a battery made from cells of identical nominal specifications connected in series and parallel, supplying a constant load in W. This calculation does not assess actual UPS runtime, battery safety or wiring feasibility, manufacturer-specific voltage ranges, protection or maximum current, variable loads, self-discharge, or effective capacity changes due to temperature, aging, voltage drop, or discharge rate.
Methods used
- Nominal-energy constant-load model (v1.0): scope Estimate using identical cells, a constant W load, and nominal voltage; region Region-independent
Method and sources
Method: nominal-energy-constant-load-v1.0. Data recorded: 2026-11-13.