Estimate pack voltage and supply duration from the series/parallel cell configuration and a constant-load energy balance

This is an estimate based on rated capacity. Actual UPS runtime depends on battery and equipment discharge characteristics and protective shutdown behavior.

Nominal value for one cell or one battery module of identical specifications.

Enter the manufacturer's nominal capacity for the assumed discharge conditions.

Actual power supplied to the load. Enter W, not a VA rating involving power factor.

Percentage of nominal capacity used. Enter 0–100%, accounting for the minimum remaining charge and other limits.

Conversion efficiency from the battery to the load. Distinguish this from round-trip charge/discharge efficiency.

Optional. Enter the manufacturer's discharge-rate limit if specified. Capacity reduction due to discharge rate is not corrected.

Results

Results update automatically when the required values are entered.

Method, applicability and sources

Calculation method

Pack voltage (V) = nominal cell voltage (V)×series count. Pack capacity (Ah) = nominal cell capacity (Ah)×parallel count. Nominal energy (Wh) = pack voltage×pack capacity. Estimated usable energy (Wh) = nominal energy×depth of discharge (%)÷100×discharge-path efficiency (%)÷100. Backup runtime (h) = estimated usable energy÷load (W). Required C-rate (1/h) = load (W)÷discharge-path efficiency as a fraction÷nominal energy (Wh).

Worked example (hypothetical values)

Example: Identical 12 V, 200 Ah batteries connected 2 in series × 2 in parallel give 24 V, 400 Ah, and 9,600 Wh. With 80% depth of discharge, 90% discharge efficiency, and a constant 960 W load, 6,912 Wh÷960 W = 7.2 hours.

Applicability and limitations

Estimate for a battery made from cells of identical nominal specifications connected in series and parallel, supplying a constant load in W. This calculation does not assess actual UPS runtime, battery safety or wiring feasibility, manufacturer-specific voltage ranges, protection or maximum current, variable loads, self-discharge, or effective capacity changes due to temperature, aging, voltage drop, or discharge rate.

Methods used

  • Nominal-energy constant-load model (v1.0): scope Estimate using identical cells, a constant W load, and nominal voltage; region Region-independent

Method and sources

Method: nominal-energy-constant-load-v1.0. Data recorded: 2026-11-13.