Thermocouple and Pt100 Temperature Conversion
Convert resistance or thermoelectric voltage to and from temperature using the sensor's standard characteristic curve.
Select a conversion direction for Pt100 or Type K. The stated temperature ranges are those of the standard reference functions.
Results
—
- Conversion conditions and breakdown
- —
Results update automatically when the required values are entered.
Method, applicability and sources
Calculation method
Pt100: R(t)=100×[1+At+Bt²] for 0–850 °C; R(t)=100×[1+At+Bt²+C(t−100)t³] for −200–0 °C. A=0.0039083, B=−5.775×10⁻⁷, C=−4.183×10⁻¹². For Type K, let E(t) be the NIST temperature-dependent polynomial, with an exponential term added at temperatures ≥0 °C. Measured voltage E_measured=E(measuring junction)−E(reference junction). Inverse conversion uses bisection within the valid range.
Worked example (hypothetical values)
Pt100 resistance at 100 °C is 138.5055 Ω (138.51 Ω after reference-table rounding). A Type K thermocouple at 100 °C produces approximately 4.096 mV when its reference junction is at 0 °C.
Applicability and limitations
Instrumentation and temperature measurement using nominal characteristics of Pt100 (100 Ω at 0 °C) and Type K thermocouples. Excludes JPt100, Pt1000, other resistance temperature detectors, non-Type-K thermocouples, individual sensor variation and tolerances, lead resistance, instrument error, noise correction, and calibration. No extrapolation beyond the reference functions' temperature ranges.
Methods used
- Pt100 nominal resistance characteristic (IEC 60751:2022 §4.2): scope −200~850 ℃、R₀=100 Ω; region Global
- Type K reference thermoelectric voltage (NIST Monograph 175 (1993) §7.3): scope −270 to 1372 °C; reference functions relative to 0 °C with reference-junction compensation; region Global
Method and sources
Method: IEC 60751:2022 §4.2/NIST Monograph 175 (1993) §7.3, ITS-90. Data recorded: 2026-11-13.