Search Tools

Thermocouple and Pt100 Temperature Conversion

Report an issue

Convert resistance or thermoelectric voltage to and from temperature using the sensor's standard characteristic curve.

Select a conversion direction for Pt100 or Type K. The stated temperature ranges are those of the standard reference functions.

What to calculate

Resistance of the sensor element only. Exclude lead resistance and similar contributions.

Results

Results update automatically when the required values are entered.

Method, applicability and sources

Calculation method

Pt100: R(t)=100×[1+At+Bt²] for 0–850 °C; R(t)=100×[1+At+Bt²+C(t−100)t³] for −200–0 °C. A=0.0039083, B=−5.775×10⁻⁷, C=−4.183×10⁻¹². For Type K, let E(t) be the NIST temperature-dependent polynomial, with an exponential term added at temperatures ≥0 °C. Measured voltage E_measured=E(measuring junction)−E(reference junction). Inverse conversion uses bisection within the valid range.

Worked example (hypothetical values)

Pt100 resistance at 100 °C is 138.5055 Ω (138.51 Ω after reference-table rounding). A Type K thermocouple at 100 °C produces approximately 4.096 mV when its reference junction is at 0 °C.

Applicability and limitations

Instrumentation and temperature measurement using nominal characteristics of Pt100 (100 Ω at 0 °C) and Type K thermocouples. Excludes JPt100, Pt1000, other resistance temperature detectors, non-Type-K thermocouples, individual sensor variation and tolerances, lead resistance, instrument error, noise correction, and calibration. No extrapolation beyond the reference functions' temperature ranges.

Methods used

  • Pt100 nominal resistance characteristic (IEC 60751:2022 §4.2): scope −200~850 ℃、R₀=100 Ω; region Global
  • Type K reference thermoelectric voltage (NIST Monograph 175 (1993) §7.3): scope −270 to 1372 °C; reference functions relative to 0 °C with reference-junction compensation; region Global

Method and sources

Method: IEC 60751:2022 §4.2/NIST Monograph 175 (1993) §7.3, ITS-90. Data recorded: 2026-11-13.