Three-Phase Power, Apparent Power and Power Factor

Report an issue

Check relationships between active, apparent and reactive power and power factor from voltage and current

For consuming loads with sinusoidal single-phase AC or balanced three-phase AC. Use RMS voltage and current.

What to calculate

For three-phase, use line-to-line voltage; for single-phase, voltage across the load.

For three-phase, use line current. Power factor is undefined at 0 A.

From 0 to 1. Enter the factor corresponding to phase displacement for a sinusoidal waveform.

If not selected, only the magnitude of reactive power is shown.

Results

Results update automatically when the required values are entered.

Method, applicability and sources

Calculation method

Single-phase: S(kVA) = V(V) × I(A) /1000. Balanced three-phase: S(kVA) = √3 × line voltage(V) × line current(A) /1000. If PF is known: P(kW) = S × PF; |Q|(kvar) = S × √((1−PF)(1+PF)). If P is known: PF = P/S; |Q| = √((S−P)(S+P)). S² = P² + Q². Q is an absolute value unless a sign is selected: lagging positive, leading negative. Distortion power from nonsinusoidal waveforms is excluded.

Worked example (hypothetical values)

Balanced three-phase, line voltage 200 V, line current 10 A and PF 0.8 give S ≈3.464102 kVA, P ≈2.771281 kW and |Q| ≈2.078461 kvar.

Applicability and limitations

Loads consuming sinusoidal single-phase AC or balanced three-phase AC. Excludes unbalanced three-phase systems, harmonics and distortion power factor, negative active power from generation or regeneration, energy totals over time, motor efficiency from shaft output, and solving for voltage or current.

Method and sources

Method: E120 balanced sinusoidal AC power v1.0 (2026-11-13). Data recorded: 2026-11-13.