Three-Phase Power, Apparent Power and Power Factor
Check relationships between active, apparent and reactive power and power factor from voltage and current
For consuming loads with sinusoidal single-phase AC or balanced three-phase AC. Use RMS voltage and current.
Results
—kW
- Apparent power S
- —kVA
- Reactive power Q
- —kvar
- Power factor
- —
Results update automatically when the required values are entered.
Method, applicability and sources
Calculation method
Single-phase: S(kVA) = V(V) × I(A) /1000. Balanced three-phase: S(kVA) = √3 × line voltage(V) × line current(A) /1000. If PF is known: P(kW) = S × PF; |Q|(kvar) = S × √((1−PF)(1+PF)). If P is known: PF = P/S; |Q| = √((S−P)(S+P)). S² = P² + Q². Q is an absolute value unless a sign is selected: lagging positive, leading negative. Distortion power from nonsinusoidal waveforms is excluded.
Worked example (hypothetical values)
Balanced three-phase, line voltage 200 V, line current 10 A and PF 0.8 give S ≈3.464102 kVA, P ≈2.771281 kW and |Q| ≈2.078461 kvar.
Applicability and limitations
Loads consuming sinusoidal single-phase AC or balanced three-phase AC. Excludes unbalanced three-phase systems, harmonics and distortion power factor, negative active power from generation or regeneration, energy totals over time, motor efficiency from shaft output, and solving for voltage or current.
Method and sources
Method: E120 balanced sinusoidal AC power v1.0 (2026-11-13). Data recorded: 2026-11-13.